Car Park Ventilation – Assisted Natural Ventilation Which must provide 2.5% free area openings of net car park floor area to comply with Approved Document B Must be split with at least 50% openings on opposing walls. System must be combined with Induction Fans Only to create 3ACH to comply with Approved Document F. Example: Area 1000m 2 Total required openings = 25m 2 Free Area Minimum elevations with at least 25% each = 6.25m 2 x 2 Aggregate elevations = 50% = 12.5m 2 6.25m 2 Free Area 6.25m 2 Free Area 12.5m 2 Free Area Car Park Area = 1000m2